Thank you for choosing to partner with National Stock Number Shop for the Circuitbreaker NSN parts you require. On this page, you can submit a quote request for Westinghouse Electric Corp part number 335C757H45, a component that can also be found by inputting NSN 5925008837670 in our search engine. Apart from this item, we also have an array of other in-demand part numbers, all of which can be traced back to a conglomerate of well-known manufacturers that we trust. Explore our expansive part catalogs by scrolling over to our menu and locate products according to manufacturer, NIIN, NSN, and more.
National Stock Number Shop works with numerous government and defense agencies, so we use CAGE Codes like 79500 to uniquely identify items in a standardized manner. Additionally, we utilize Federal Supply Classes (FSCs) to organize our stock, ensuring customers can find Westinghouse Electric Corp parts under the FSC 5925 Circuit Breakers with ease. With this in mind, we encourage you to complete the RFQ form below for NSN 5925008837670 or any others, and see how we can provide you with a customized sourcing solution. For one-on-one assistance, contact us via phone or email at any time; we are available around the clock for customer inquiries!
Note : We Will Not Share Your Information To Any Third Parties.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-883-7670 Item PartTypeName: CIRCUIT BREAKER | 5925 | 008837670 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
335C757H45 | 5 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.190 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.000 INCHES NOMINAL |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 208.0 AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 15.000 MINIMUM AT 200 PCT AND 45.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
CWJK | CASE MATERIAL | PLASTIC |
THSD | THREAD SERIES DESIGNATOR | UNC |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.812 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AKPX | POLE QUANTITY | 1 |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 SINGLE LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
FREQ | FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 2 SCREW |