Thank you for choosing to partner with National Stock Number Shop for the Circuitbreaker NSN parts you require. On this page, you can submit a quote request for Sensata Technologies Inc part number APGN-666-1-66-252, a component that can also be found by inputting NSN 5925011187438 in our search engine. Apart from this item, we also have an array of other in-demand part numbers, all of which can be traced back to a conglomerate of well-known manufacturers that we trust. Explore our expansive part catalogs by scrolling over to our menu and locate products according to manufacturer, NIIN, NSN, and more.
National Stock Number Shop works with numerous government and defense agencies, so we use CAGE Codes like 81541 to uniquely identify items in a standardized manner. Additionally, we utilize Federal Supply Classes (FSCs) to organize our stock, ensuring customers can find Sensata Technologies Inc parts under the FSC 5925 Circuit Breakers with ease. With this in mind, we encourage you to complete the RFQ form below for NSN 5925011187438 or any others, and see how we can provide you with a customized sourcing solution. For one-on-one assistance, contact us via phone or email at any time; we are available around the clock for customer inquiries!
Note : We Will Not Share Your Information To Any Third Parties.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-118-7438 Item Description: Circuitbreaker | 5925 | 011187438 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Apgn-666-1-66-252 | 5 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
TTQY | Terminal Type And Quantity | 6 TAB W/SCREW |
AKPX | Pole Quantity | 3 |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
CPLM | Maximum Continuous Load Current Rating Per Pole | 2.5 AMPERES AC ALL LOCATIONS |
MRC | Decoded Requirement | Clear Text Reply |
AEFN | Nonturn Device Location | AT 12 OCLOCK AND AT 3 OCLOCK AND AT 9 OCLOCK |
AJWX | Mounting Surface To Terminal End Distance | 2.232 INCHES MAXIMUM |
FREQ | Frequency In Hertz | 50.0 SINGLE LOCATION OR 60.0 SINGLE LOCATION |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 3500.0 AC ALL LOCATIONS |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC ALL LOCATIONS |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC ALL LOCATIONS |
AEFP | Nonturn Device Radius | 0.656 INCHES NOMINAL |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRQ | Reset Method | MANUAL |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 115.0 ALL LOCATIONS |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
THSD | Thread Series Designator | UN |
CPRW | Actuator Function | TRIP-RESET |
ADTV | Case Material | PLASTIC |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
CPRX | Actuator Position Designation | AT POLE TWO |
AAJE | Thread Pitch Diameters | +0.4752/+0.4787 INCHES |
AXHR | Mounting Facility Type And Quantity | 1 THREADED BUSHING W/PANEL SEAL |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
CQJX | Nominal Thread Size | 0.500 INCHES |
AEFQ | Nonturn Device Length | 0.130 INCHES NOMINAL |
AEFS | Nonturn Device Diameter | 0.151 INCHES MINIMUM AND 0.161 INCHES MAXIMUM |
ADAQ | Body Length | 2.000 INCHES NOMINAL |
BBRJ | Special Handling Feature | MAGNETIC |
APNQ | Arc Quenching Method | MAGNETIC BLOWOUT |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 0.750 INCHES NOMINAL |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 1.530 INCHES NOMINAL |
ABXD | Bushing Length | 0.625 INCHES NOMINAL |
PKWT | Unpackaged Unit Weight | 9.000 OUNCES |
ADAT | Body Width | 2.250 INCHES NOMINAL |
CMLP | Thread Quantity Per Inch | 32 |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 150.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
AFJN | Fragility Factor | MODERATELY RUGGED |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CQXF | Inclosure Protection Type For Which Designed | HERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT |