Thank you for choosing to partner with National Stock Number Shop for the Circuitbreaker NSN parts you require. On this page, you can submit a quote request for Harsco Corporation part number 31-065, a component that can also be found by inputting NSN 5925007623790 in our search engine. Apart from this item, we also have an array of other in-demand part numbers, all of which can be traced back to a conglomerate of well-known manufacturers that we trust. Explore our expansive part catalogs by scrolling over to our menu and locate products according to manufacturer, NIIN, NSN, and more.
National Stock Number Shop works with numerous government and defense agencies, so we use CAGE Codes like 93568 to uniquely identify items in a standardized manner. Additionally, we utilize Federal Supply Classes (FSCs) to organize our stock, ensuring customers can find Harsco Corporation parts under the FSC 5925 Circuit Breakers with ease. With this in mind, we encourage you to complete the RFQ form below for NSN 5925007623790 or any others, and see how we can provide you with a customized sourcing solution. For one-on-one assistance, contact us via phone or email at any time; we are available around the clock for customer inquiries!
Note : We Will Not Share Your Information To Any Third Parties.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-762-3790 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007623790 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
31-065 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 8.875 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 8.437 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC AND 150.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 NOMINAL AT 150 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND HERMETICALLY SEALED |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 10.125 INCHES NOMINAL |
ADAT | BODY WIDTH | 8.250 INCHES NOMINAL |
ADAU | BODY HEIGHT | 5.500 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.146 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.313 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.718 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.500 INCHES NOMINAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC AND 10000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |