| MRC | Criteria | Characteristic |
|---|
| AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| ABTD | MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
| ADAQ | BODY LENGTH | 5.844 INCHES NOMINAL |
| ADAT | BODY WIDTH | 3.096 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.546 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.032 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.032 INCHES NOMINAL |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.218 INCHES NOMINAL |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.609 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 4 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE AND 8 SLOT |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC FOURTH LOCATION |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC SECOND LOCATION |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC THIRD LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 107.0 DC FIRST LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC FOURTH LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SECOND LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC THIRD LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC FOURTH LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SECOND LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC THIRD LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT FOURTH LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SECOND LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT THIRD LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | UNDERVOLTAGE FIRST LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC FIRST LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC FOURTH LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SECOND LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC THIRD LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS FIRST LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY FOURTH LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SECOND LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY THIRD LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 FOURTH LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 SECOND LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 THIRD LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE,TWO,THREE,AND FOUR LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT FOURTH LOCATION |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT SECOND LOCATION |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT THIRD LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| CWJK | CASE MATERIAL | PLASTIC |
| FEAT | SPECIAL FEATURES | FOUR TERMINALS ON POLE ONE |
| FREQ | FREQUENCY IN HERTZ | 400.0 FOURTH LOCATION |
| FREQ | FREQUENCY IN HERTZ | 400.0 SECOND LOCATION |
| FREQ | FREQUENCY IN HERTZ | 400.0 THIRD LOCATION |
| TEST | TEST DATA DOCUMENT | 49956-G166010 DRAWING (THIS IS THE BASIC GOVERNING DRAWING,SUCH AS A CONTRACTOR DRAWING,ORIGINAL EQUIPMENT MANUFACTURER DRAWING,ETC.; EXCLUDES ANY SPECIFICATION,STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAW |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 10 THREADED STUD |