If your operations demand dependable items that fall under the NSN 5925-00-533-1426, look no further than the expansive product list featured on this page. For your convenience, all NSN 5925-00-533-1426 part numbers that we have in stock like TEB122015, and others are listed below with their respective manufacturer. Should any of these products match your requirements, you may click on the “RFQ” button presented next to each listing to access our online quote request service. By providing our team with information like your desired part quantity, pricing, and fulfillment speed on the form you are directed to, we can offer a procurement solution that best accommodates your needs within 15 minutes of our receipt and review.
You never have to compromise any of your needs when you shop with us, as we always aim to offer competitive pricing and delivery times for every order. Furthermore, quality is a fundamental cornerstone of our operations, and we carry out various practices to guarantee the fit, form, and function of our NSN 5925-00-533-1426 products, starting with strictly sourcing from trustworthy NSN parts suppliers and manufacturers. To learn more about our diverse commitments and see why so many customers steadily depend on our services, connect with us by form, phone, or email at your earliest convenience.
Item Name | Circuit Breaker |
Federal Supply Group (FSG) | Electrical and Electronic Equipment Components |
Federal Supply Class (FSC) | 5925 Circuit Breakers |
National Item Identification Number (NIIN) | 00-533-1426 (005331426) |
NCB Code | USA (00) |
Manufacturer | General Electric Company |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.312 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.812 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.874 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC ALL LOCATIONS AND 10.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO AND BETWEEN POLE THREE AND FOUR |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQQC | TRIP RELEASE DUTY CYCLE | CONTINUOUS ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 65.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 400.000 MAXIMUM AT 150 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |
Relevant Components for NSN - 5925-00-533-1426, 5925005331426 | ||||
5995-01-010-0452 (5995010100452) | 5910-01-029-7498 (5910010297498) | 5950-01-448-2088 (5950014482088) | 5910-00-213-6124 (5910002136124) | |
5905-01-340-6179 (5905013406179) | 5910-00-983-8880 (5910009838880) | 5925-01-394-9478 (5925013949478) | 5905-01-219-6985 (5905012196985) | |
5935-01-062-0549 (5935010620549) | 5930-01-693-5473 (5930016935473) | 5996-01-510-1164 (5996015101164) | 5998-01-481-4467 (5998014814467) | |